Requirements for piling and drilling
How to pile and drill safely near our assets.
Calibration
You can't begin the work until we've received evidence of the equipment’s calibration.
Daily checks
Carrying out some simple daily checks will help avoid damage to assets.
- If possible, remove the paper record or download the instrument after each days monitoring session and ensure that it is safely stored or given to the relevant person
- Make sure levels have not been exceeded
- Check that the instrument is clean and dry before use
- Charge the battery if necessary
Distance from pipes
We have set safe distances for piling and drilling near pipes.
Type of asset |
Size of piling and drilling exclusion zone |
Large main | 6 metres around the asset |
Small main | 6 metres around the asses |
Aqueducts | 20 metres around the asset |
Peak Particle Velocity limits and monitoring
To prevent any damage, levels of Peak Particle Velocity must be below 1.5mm per second.
The equipment should be constantly monitored. Monitoring equipment must be level (within 10 degrees) and placed on or at the structure nearest to the vibration source.
If you use a vibrographs sensor, it must be fixed to the structure being monitored by bolting, using epoxy resin, or sandbagging.
Sandbags must be loosely filled and placed so that its sides touch the ground around the geophone pack. You must ensure the geophone pack remains level.
Never site the equipment on a paving slab, as this may independently move. This can cause inaccurate readings, higher than the strucure is actually subjected to.
Make sure the monitoring equipment it is not knocked or disturbed by objects, people or animals. This can also lead to false readings.
Vibration levels that cause damage depend on the peak particle velocity and the frequency it occurs. Damage to an asset is likely where PPV is high when its frequency is low.
Work should immediately stop if PPV exceeds 1.5mm/s and you should notify us straight away.
All team members on site should be aware of these limits.
Why we measure Peak Particle Velocity
We measure ground vibrations using Peak Particle Velocity in millimetres per second.
This measures the movement of molecular particles in the ground. It does not measure surface movement.
Piling, driving, dynamic compaction, blasting and heavy machinery can all cause ground vibrations.
These vibrations can have an impact on the surrounding area.
They can affect buildings, cause structural damage and disturb local residents.
Ground vibrations can cause structural damage to buildings once they go above 15 mm/s.
We set vibration limits to avoid damage to infrastructure, the environment and disturbance to local people.
Contact the Asset Protection Team
The Asset Protection team help commercial developers to understand and plan what needs to be done when working near our pipes and other infrastructure.
You can contact the Asset Protection team by email and phone.
- Email the Asset Protection team at asset.protection@severntrent.co.uk
- Call the Asset Protection team on 02477 716185
The team are available:
- Monday to Thursday: 9am to 5pm
- Friday: 9am to 4.30pm
Please leave a voicemail if you're unable to get through to the team or call outside office hours. We'll do our best to get back to you the next working day.